ABB PCS 100 UPS-1 Facility Wide UPS
150kVA - 3000kVA
APPLICATIONS: Facility-WIde UPS , Plant, Labs, Robotics, Process Controls, Semiconductors, Pharmaceuticals, Plastic Extrusion, Metals and Mining.
SOLVES: All Undervoltage, Overvoltage, Voltage Sags, Surges, unreliable utility voltage and internally-derived Voltage Issues.
Provides battery or other storage runtime for
Complete Power Outages.

Technology Choice: BEST IN CLASS - Complete Facility UPS System. Single Conversion. Generator/ATS Compatibile.
Why? Measures incoming voltage, corrects by Inverter Intercept. Provides runtime via Battery or Ultracapacitors.

Power Correction Level 1: +/- 0-4% Variation on Output Power
Input Voltage Tolerance: Wide Deep Voltage Sags, Complete Outages
Sizes: 150kVA, 300kVA, 450kVA, 600kVA, 750kVA, 900kVA, 1050kVA, 1200kVA, 1350kVA, 1500kVA, 1800kVA, 2400kVA, 3000kVA,
Input Voltage: 208V, 400V, 480V Three Phase
Output Voltage Regulation: +/- 0=3%
Runtimes: Battery or Ultracapacitor to specification,
Generator/ATS Compatible
OPTIONS: Maintenance Bypass
CLASS: UPS, Industrial UPS
CORRECTS: Voltage Sags and Power Interruptions and Outages
APPLICATIONS: Entire Facility UPS , Plant, Labs, Robotics, Plant and Process, Semiconductors, Pharmaceuticals, Plastic Extrusion, Metals and Mining, All Processes and Controls.
ROI: Reduced PCB and Board Failures, Reduced Downtime, Reduced Maintenance Costs. Typically 3-5 Years.
VIDEO: ABB PCS 100 UPS-1 Industrial UPS
VIDEO: ABB PCS100 Active Voltage Conditioner
Industrial Facility Wide UPS for Large Applications
Facilities requiring entire service entrance pickup, or Facility Wide Outage Protection with an Industrial UPS can use the PCS 100 UPS-1 to solve just that problem. Entire critical load centers can be combined for ultimate protection and runtime against all sags and complete power outages. Runtimes are variable to customer requirements for time to shut down equipment and save processes, or provide the cutover time to a generator backup solution.
The PCS100 UPS-I is a high performance, high efficiency UPS system that ensures protection from power quality events, such as deep sags or short-term outages, enabling continuous power supply to modern industrial processes. The PCS100 UPS-I uses a modular energy storage and inverter system to supply continuous power during utility events. The PCS100 UPS-I provides flexibility in the choice of energy storage, ultracapacitors or batteries to achieve the desired runtime solution.
UPS-1 vs Traditional UPS
Plant Facilities using large industrial devices that have high inrush currents cannot be supported by a traditional UPS designed for Data Center applications. Customers seeking a Correction device with runtime to correct more than sags and voltage, need to seek out a Industrial Designed System to withstand the constant current variations and inrush properties of a Process Plant, Factory, or high amperage draw machinery.
Runtime and Generator Applications
Battery systems can deliver autonomy for specified runtime duration. Ultracapacitors provide seconds of protection for short power quality events, which are the most common power quality problems around the world. Ultracapacitors have extremely high power density and long lifetime resulting in a very compact and low maintenance solution. Harsh electrical environments are often found in modern industry. The UPS-1 is also compatible with generator Applications. A Battery Bank with runtime enough to transfer to generator with ATS are available.
How the ABB PCS 100 UPS-1 Works
High Efficiency Design design for Industrial UPS Applications
The PCS100 UPS-I uses a robust high-speed power electronic disconnect switch to connect the load to the utility. The modular inverter construction and fail-safe electromechanical bypass provides the highest system availability. Coupled with the small footprint and easy serviceability, this low maintenance, high efficiency industrial UPS is the solution for all power large facility and plant applications.
When the utility voltage is within a user defined range, the load is supplied directly by the utility. When a sag, surge or outage occurs, the PCS100 UPS-I immediately transfers the load onto its inverter and energy storage. When the utility voltage returns to within specification the PCS100 UPS-I will seamlessly transfer the load from the inverter back to the utility.

Key benefits of the PCS 100 UPS Industrial UPS System
- Robust fail-safe modular industrial design
- Long lifetime energy storage • Small footprint
- Highest efficiency and availability
- Low maintenance requirements
- Easy serviceability Key features
- Very high efficiency (99% typical)
- Designed specifically for industrial loads (motors, drives, transformers, production tools)
- Modular design providing high reliability and typically 30 minutes MTTR (mean time to repair)
- Very high fault current capacity
- Advanced ultracapacitor or high discharge rate battery storage
- Generator walk-in algorithm for a controlled transfer of the load to backup generators
- Ratings from 150 kVA to 3000 kVA and voltages • 208 Vac to 480 Vac
PCS100 UPS-I advantages compared to alternative solutions
- Robust with high availability
- Designed for harsh industrial electrical environments
- Modular design • Lowest cost of ownership
- Highest efficiency • Long lifetime energy storage • Small footprint • Flexible energy storage options (ultracapacitors or VRLA batteries)
- Very few other options of systems in size range
Request Pricing - Brochures - Help!
Get Help with Sizing Your UPS System, Runtimes and Power Requirements for Your Installation
Ask Us Any Question!
AVR Model Voltage Performance
208V PCS 100 UPS-1
- Input Voltage Swings of +/- 10% VAC
- Displacement Power Factor of Connected Load 0.5 lagging to 0.9 leading
- Overload Capability-Inverter 110% for 30s
- Voltage Settling time ≤ 5 ms (typical)
- Output Frequency50 or 60 Hz
Inverter frequency equals the supply frequency. - Output Frequency50 or 60 Hz
Inverter frequency equals the supply frequency. - Voltage distortion< 2.5% THDv for linear loads
- Fault capacity (short circuit)120% of rated current
- Voltage unbalance (negative / positive sequence)<3% for 100% unbalanced loads

400V PCS 100 UPS-1
- Input Voltage Swings of +/- 10% VAC
- Displacement Power Factor of Connected Load 0.5 lagging to 0.9 leading
- Overload Capability – Inverter 110% for 30 s
- Voltage Settling time ≤ 5 ms (typical)
- Output Frequency50 or 60 Hz
Inverter frequency equals the supply frequency. - Output Frequency50 or 60 Hz
Inverter frequency equals the supply frequency. - Voltage distortion< 2.5% THDv for linear loads
- Fault capacity (short circuit)120% of rated current
- Voltage unbalance (negative / positive sequence)<3% for 100% unbalanced loads

480V PCS 100 UPS-1
- Input Voltage Swings of +/- 10% VAC
- Displacement Power Factor of Connected Load 0.5 lagging to 0.9 leading
- Overload Capability – Inverter 110% for 30 s
- Voltage Settling time ≤ 5 ms (typical)
- Output Frequency50 or 60 Hz
Inverter frequency equals the supply frequency. - Output Frequency50 or 60 Hz
Inverter frequency equals the supply frequency. - Voltage distortion< 2.5% THDv for linear loads
- Fault capacity (short circuit)120% of rated current
- Voltage unbalance (negative / positive sequence)<3% for 100% unbalanced loads

Snapshot, Tech Specs, PDFs
Download our brochure and user guides to learn more about our products.
FGC Customer Advantage
Comprehensive Lifetime Service Support for your AVR Equipment
7 x 24 Emergency Service Response
24x7 emergency service Services through FGC Services and Response Platform
Preventative Maintenance Plans Provided by FGC Services
Keep all your systems free of downtime with Preventative Maintenance Programs.
Plans include Full Service, Preventative Maintenance Plus Emergency Response, and PM Only.
100% parts coverage
Parts coverage inside your warranty period, extended plans available for Annual or Multi-Year Programs
Asset Management Program
Roll all your Critical Assets and Maintenance Programs into one location - Facility Keys Preferred Platform
7x24 Emergency Response

National Service Coverage for Emergency Calls, On-Site Response, and Remediation.
Voltage Regulator vs. UPS: What are my Choices?
The differences between AVR, AVC, and UPS mainly depend on the construct of your electrical loads, and the power issues you wish to correct.
Correcting Voltage Not Outages
Most Data Center Designed UPS Systems are built to withstand minutes if not longer of complete power absence. Being designed to make almost perfect power until it is not there, systems are designed with highly efficient inverter systems and other components. Loads on these systems are often constant, non-reactive loads, and low in-rush. These systems, however, does not perform well in an active load environment, high in-rush current environment, and do not take in large input windows of voltage and repair them.
Ferrups Voltage Regulator UPS

Ask about combination Voltage Regulator UPS
Remote Diagnostic Services for Rapid Response
Uptime assurance
- Continuous monitoring for early detection of trends and operating anomalies
- Analysis and interpretation of alarm and status messages
Rapid incident response
- Automatic transmission of data for analysis
- Concurrent diagnosis and dispatch of engineer to site
- Shipment of parts for corrective maintenance
Increased insight and ease of management
- Notification of operating conditions that may impact system health
- Periodic trend and analysis reports
- Integration of remote and on-site services to ensure business continuity